The first sign is usually a letter, not an inspector. An amateur radio operator a few miles out notices a rise in the noise floor across the HF bands, traces it to a bearing, and files a complaint with the FCC or writes to the facility directly. The equipment inside the fence line passed every safety inspection and every electrical code review. None of that answers the question that just arrived: does Part 15 require anything from an already-operating site, and what does a mining operator actually do when a complaint like this shows up?
The honest answer is that the exposure was built in from the first day of construction, not created by any single mistake. Hundreds or thousands of switching power supplies running continuously generate electromagnetic noise as a byproduct of how they work, not as a defect. Most of that noise is harmless. Some of it lands precisely where the FCC’s amateur radio allocations sit, and that overlap – not any particular wiring error – is what turns a compliant facility into the subject of a complaint.
What Part 15 Actually Requires
47 CFR Part 15 of the FCC’s rules governs unintentional radiators – electronic devices that emit radio-frequency energy as a side effect of normal operation rather than on purpose. ASIC miners and their power supplies fall squarely in this category, the same one that covers computers, LED drivers and most switching electronics sold in the United States.
Part 15 equipment is sold under one of two emission limit sets. Class A covers equipment marketed for commercial, industrial and business use and carries the looser limit. Class B covers equipment intended for the residential environment and must meet a stricter limit, because the FCC assumes home installations sit closer to broadcast and amateur receivers. Most ASIC miners are verified to Class A, which is the correct and lawful classification for equipment sold into industrial hosting facilities – but Class A’s looser limit is also precisely why a large concentration of Class A equipment, however individually compliant, can still produce a detectable rise in the ambient RF noise floor around the site.
The rule that matters most once a complaint exists is Part 15.5: even fully compliant unintentional radiators must accept interference they receive, but they must also not cause harmful interference to a licensed service – and if they do, the operator of the interfering equipment is required to correct the problem, promptly, upon notification. Compliance at the point of sale does not end the operator’s obligation. The FCC’s enforcement model here is complaint-driven rather than pre-emptive: there is no routine site inspection program for installed equipment, which means the first the FCC’s Enforcement Bureau typically hears about a mining facility is when someone files a complaint, not before.
Why HF Radio Is the Band That Actually Complains
Switching power supplies generate harmonics of their switching frequency, and the fundamental switching frequencies used in high-density ASIC power supplies commonly fall in a range whose harmonics land across the HF spectrum – the same 3-30 MHz range that amateur radio operators use for long-distance contacts and that is far more sensitive to a rising noise floor than most people expect, because HF reception depends on picking a weak signal out of exactly that kind of broadband electrical noise. A facility can be fully inaudible on FM broadcast or cellular bands and still be clearly audible to a ham radio operator running HF, which is why complaints in this space come disproportionately from that community rather than from ordinary neighbors who would notice acoustic noise first. Our grounding and bonding guide covers the on-site half of this – EMI that corrupts your own monitoring and network equipment – but off-site RF leakage is a distinct exposure that grounding alone does not fully resolve, because radiated emissions travel through the air, not just through improperly bonded conductors.
The Filtering and Siting Checklist, in the Order It Actually Gets Cheaper
Every mitigation available here gets more expensive the later it is applied, which makes the sequence matter as much as the individual measures:
- Ask for the Declaration of Conformity before you buy. Part 15 verification places the compliance burden on the manufacturer, and a legitimate ASIC vendor can produce the test report or DoC on request. This does not eliminate the exposure described above, but it confirms the hardware itself is not out of spec, which narrows any later investigation to facility-level causes.
- Specify power-line filtering at the PDU, not the rack. Conducted emissions traveling back out through the electrical service are often the larger contributor to off-site radiated noise than anything leaving the miner enclosure directly, because the service entrance conductors and utility wiring act as an unintentional antenna. Filtering at the point where the facility’s power distribution meets the utility connection addresses the whole fleet at once rather than unit by unit.
- Keep shielded cable runs and separation distances the grounding guide already specifies. The same practices that prevent EMI from corrupting your own network traffic – shielded twisted pair, fiber for inter-building links, separated power and signal pathways – reduce the facility’s overall RF signature as a side effect, so this is not a second budget line if the grounding work is already specified correctly.
- Weigh setback distance the same way the noise-ordinance playbook already does. Radiated field strength falls off with distance, so a site with real separation from the nearest residence or amateur station has real margin that a tightly sited facility does not. This is the same siting logic used for acoustic setbacks, just for a different kind of emission.
- Treat retrofit filtering as the expensive option, not the fallback. Adding line filters and shielding after a complaint means re-entering live electrical gear and coordinating downtime across an operating fleet, instead of specifying the same hardware once during the original electrical design.
Three Postures, and What Each One Actually Costs
There is no single correct answer here, because the right posture depends on what sits near the site – but the trade-off should be made deliberately rather than by default:
| Posture | Upfront cost | What it actually buys |
|---|---|---|
| Do nothing beyond buying compliant hardware | Lowest | Lawful, but leaves the facility fully exposed to a Part 15.5 correction demand if a complaint lands – and correction after the fact costs more, not less, than doing it up front |
| Line filtering and grounding specified at construction | Moderate | Addresses the majority of realistic complaint scenarios at the point where it is cheapest to implement, without a dedicated RF study |
| Pre-construction RF site survey plus shielding | Highest | Justified near a site with existing amateur radio activity, a sensitive receiver nearby, or a jurisdiction that has already seen RF complaints against industrial equipment – overkill for an isolated rural parcel |
Most hosted mining sites sit far enough from dense residential or amateur-radio-active areas that the moderate posture is the economically sensible default; the survey-and-shield posture earns its cost only where the site genuinely sits near a population of HF operators or an already-sensitive receiver, the same way a full acoustic study only earns its cost near a receptor close enough for noise ordinances to matter.
What to Do When a Complaint Actually Arrives
Respond promptly and in writing – Part 15.5’s correction obligation is genuine, and ignoring a documented complaint converts a filtering problem into an enforcement problem. Ask the complainant for specifics: frequency, time of day, and whether the interference is continuous or intermittent, because that detail usually points straight at which mitigation layer above is missing. Our environmental compliance guide covers the broader community-relations playbook for this kind of outside complaint – early, direct communication and a documented remediation plan read the same way to a regulator whether the complaint is about decibels or radio noise, and our guide to neighbor nuisance claims covers what happens if a complaint escalates past a regulatory letter into litigation, a path RF complaints can also take if left unaddressed.
Before You Build: A Short Checklist
- Confirm the hardware vendor can produce a Part 15 Declaration of Conformity for the specific PSU and controller models being deployed.
- Specify power-line filtering at the PDU and the grounding/shielding practices already required for your own monitoring network, during electrical design, not after energization.
- Check whether the parcel sits near a known concentration of amateur radio activity or a sensitive receiver before finalizing siting, the same diligence already applied to acoustic setbacks.
- Assign one person ownership of any interference complaint that arrives, with a documented response process, rather than leaving it to whoever happens to answer the phone.
None of this is a substitute for review by an RF or compliance engineer on a specific site – this guide is grounding for that conversation, not a replacement for it. Rax Mining’s hosted facilities are built with the electrical design practices this guide describes already specified at construction. Contact us to discuss hosting your fleet in a facility built this way from the start, or see our natural-gas MDU hosting option for a purpose-built alternative to retrofitting an existing site.